Fire Riser Room Sign Height Requirement
From the 2016 edition of nfpa 13.
Fire riser room sign height requirement. This change correlates the fire sprinkler requirement for s 1 occupancies in chapter 9 meaning mini. The fire sprinkler riser assembly the fire alarm control panel fire alarm manual pull station spare sprinkler heads storage box and the document box for as built drawings shall be located within the room. In some instances the system s fire pump and fire alarm control panel are also located in the sprinkler riser room and additional signage is required if they are. Signage is required on the access doors to fire pump and riser rooms and shall consist of letters at least two inches in height.
Section 6 6 4 of nfpa 13 stipulates sign requirements for all control drain venting and test connection valves while section 8 16 1 1 expands on the guidance for control valves. The signs shall be a minimum size of 18 inches 457 mm by 12 inches 305 mm. Most fire sprinkler system valves must be identified with metal or rigid plastic signs. 6 6 4 identification of valves.
Ifc section 1023 9 1 signage requirements. The letters designating the identification of the interior exit stairway and ramp shall be not less than 1 1 2 inches 38 mm in height. Fire equipment room minimum requirements fire riser room the fire equipment room shall be located within the building footprint. Stairway identification signs shall comply with all of the following requirements.
What is clear is that they are required for your system to be in compliance with the. And some local codes require riser rooms to house remote unit fire alarm panels connected to the master fire alarm panel in multi family residential occupancies.